Application |
---|
Media | Water, glycol solutions, backlash, oils |
Medium note | low viscosity oils with viscosity: ? 40 mm?/s (40 °C) | high viscosity oils with viscosity:> 40 mm?/s (40 °C) |
|
Measured medium temperature [°C] | -20…90 |
Pressure strength [bar] | 100 |
MAWP (for CRN application) [bar] | 100 |
Electronic data |
---|
Operating voltage [V] | 18…30 DC |
Current consumption [mA] | <100 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 10 |
Inputs/outputs |
---|
Number of inputs and outputs | Number of digital outputs: 2 , Number of analog outputs: 1 |
Outputs |
---|
Total number of outputs | 2 |
Output signal | Switching signal, analogue signal, frequency signal, IO-Link, (configurable) |
Electric Physical version | PNP/NPN |
Number of digital outputs | 2 |
Output function | normally open / normally closed, (parameterizable) |
Max. voltage drop of switching output DC [V] | 2.5 |
DC load current of switching output DC [mA] | 250 |
Number of analog outputs | 1 |
Analog current output [mA] | 4…20, (scalable) |
Maximum load [?] | 350 |
Short-circuit protection | yes |
Short-circuit protection type | clocked |
Overcurrent protection | yes |
Output frequency [Hz] | 0…1000 |
Measuring/setting range |
---|
Probe length L [mm] | 45 |
Operating mode | Relative, Absolute liquid, Absolute gaseous |
Note on setting range | |
Liquid media |
---|
Measuring range [m/s] | 0.04…3 |
N parameter setting within [m/s] | 0…6 |
Gases |
---|
Measuring range [m/s] | 2…100 |
Parameter setting within [m/s] | 0… 200 |
Temperature control |
---|
Measuring range [°C] | -20… 90 |
Resolution [°C] | 0.2 |
Accuracy/Uncertainty |
---|
Flow rate control |
---|
Temperature drift [cm/s x 1/K] | 0.003 m /s x 1/K ( 70 °C) |
Max. environment) [K/min] | 100 |
Accuracy (in measuring range) | ± (7% MW + 2% MEW), (for relative mode in the measuring range c:, Water: 20…70 °C, inlet pipe length: 1.5 m, DN25 (DIN 2448), installation position according to the instructions, Accuracy may differ for other media and mounting positions.) |
Repeatability | 0.05 m/s, (Water, Flow velocity: 0.05…3 m/s) |
Temperature control |
---|
Temperature drift | ± 0.005 K/°C |
Accuracy [K] | ± 0.3 / ± 1, (Water, Flow velocity: 0.3…3 m/s / backlash, Flow velocity:> 10 m/s) |
Reaction time |
---|
Flow rate control |
---|
Response time [s] | 0.5, (T09, Water, glycol: 0.8 s, backlash: 7 s, oil: 1.8 s, each T09) |
Temperature control |
---|
Trip response time T05 / T09 [s] | 1.5 (T09), (Water, Flow rate: 0, 3…3 m/s) |
Software / Programming |
---|
Parameter selection | Hysteresis / window, normally open/normally closed, switching logic, current/frequency output, medium selection, damping, teach-in function, display can be rotated and switched off, standard unit of measure, process value color |
Interfaces |
---|
Communication interface | IO-Link |
Transmission method | COM2 (38.4 kBaud) |
IO-Link test | 1.1 |
SDCI standard | IEC 61131-9 |
IO-Link device ID | 533 d / 00 02 15 h (REL) |
Profiles | Smart Sensor: Process Data Variable, Device Identification, Device Diagnosis |
SIO Mode | yes |
Desired port type | A |
Analog operating data | 2 |
Binary operating data | 2 |
Minimum operating cycle time [ms] | 3 |
Operating conditions |
---|
Ambient temperature [°C] | -40…80 |
Storage temperature [°C] | -40…100 |
Degree of protection | IP 65, IP 67 |
Tests / approvals |
---|
EMC | |
Impact resistance | DIN EN 60068-2-27 | 50 g (11 ms) |
|
Vibration resistance | DIN EN 60068-2-6 | 20 g (10…2000 Hz) |
|
MTTF [years] | 180 |
UL Certification | UL Registration Number | I003 |
|
Mechanical data |
---|
Weight [g] | 311.5 |
Material | stainless steel steel (1.4404 / 316L), stainless steel steel (1.4310 / 301), PBT-GF20, PBT-GF30 medium | stainless steel steel (1.4404 / 316L), gasket: FKM |
Process connection | M18 x 1.5 female thread |
Displays / Controls |
---|
Display | Display | 6 x LED, green (%, m/s, l/min, m?/h, °C, 10?) | Output status | 2 x LED, yellow | Measured values | alphanumeric display, red/green 4 digits |
|
Notes |
---|
Notes | MW = Measured value | MEW = Upper limit of measuring range | 540 d / 00 02 1ch (LIQU) | 547 d / 00 02 23 h (GAS) |
|
Packing quantity | 1 piece |
Electrical connection |
---|
Connection | Connector: 1 x M12, Contacts: gold-plated |