Application |
---|
Measuring element | Ceramic capacitive pressure cell |
Application | Hygienic systems |
Media | Viscous media or liquids with suspended solids, Liquid or gaseous media |
Measured medium temperature [°C] | -25…125, (150 max. 1h) |
Pressure strength | |
Min. burst pressure | |
Vacuum resistance [mbar] | -1000 |
Type of pressure | relative pressure |
No dead space | yes |
MAWP (for use according to CRN) [bar] | 50 |
Electronic data |
---|
Operating voltage [V] | 18…30 DC |
Min. insulation resistance [M?] | 100, (500 V DC) |
Protection class | III |
Reverse polarity protection | yes |
Built-in Watchdog | yes |
2-wire |
---|
Current consumption [mA] | 3.5…21.5 |
Power-on delay time [s] | 1 |
3-wire |
---|
Current consumption [mA] | <45 |
Power-on delay time [s] | 0.5 |
Inputs/outputs |
---|
Number of inputs and outputs | Number of analog outputs: 1 |
Outputs |
---|
Total number of outputs | 1 |
Output signal | analog signal |
Number of analog outputs | 1 |
Analog current output [mA] | 4…20, (scalable) |
Maximum load [?] | 700, (Ub = 24 V, (Ub - 9 V) / 21.5 mA) |
Prot short circuit protection | yes |
Overcurrent protection | yes |
Measuring/setting range |
---|
Measuring range | -1…10 bar | -14.5…145 psi | -0.1…1 MPa |
|
Analogue trigger point | -1…8 bar | -14.5…116 psi | -0.1…0.8 MPa |
|
Analog endpoint | 1…10 bar | 14.5…145 psi | 0.1…1 MPa |
|
In increments | 0.005 bar | 0.1 psi | 0.0005 MPa |
|
Factory setting | ASP = 0.0 bar | AEP = 10.0 bar | |
|
Precision/Error |
---|
Repeatability [% of range] | <± 0.1, (for temperature changes <10 K, Turn down 1:1) |
Deviation from characteristic [% of range] | <± 0.2 (nach DIN EN 61298-2), (incl. Constriction drift, zero point error and error, non-linearity, hysteresis, Turn down 1:1) |
Linearity deviation [% span] | <± 0 ,15, (Turn down 1:1) |
Hysteresis deviation [% of range] | <± 0.15, (Turn down 1:1) |
Long-term stability [% of range] | <± 0.1, (Turn down 1:1, per year) |
Zero point temperature coefficient [% of measuring range / 10 K] | <± 0.05, (0...70 °C) |
Temperature coefficient of span [% of span / 10 K] | <± 0.15, (0...70 °C) |
Response time |
---|
Analog output damping dAA [s] | 0…4 |
2- wired |
---|
Analogue output step response rise time [ms] | 30 |
3 -wired |
---|
Analogue output step response rise time [ms] | 7 |
Interfaces |
---|
Communication interface | IO-Link |
Transmission method | COM2 (38 ,4 kBaud) |
IO-Link check | 1.1 |
IO-Link device ID | 662 d / 00 02 96 h |
Profiles | Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000) |
SIO mode | none |
Desired port type | A |
Analog operating data | 3 |
Minimum operating time its cycle [ms] | 3.2 |
Operating conditions |
---|
Ambient temperature [° C] | -25…80 |
Storage temperature [°C] | -40…100 |
Degree of protection | IP 67, IP 68, IP 69K |
Tests / approvals |
---|
EMC | DIN EN 61000-6-2 | | DIN EN 61000-6-3 |
|
Impact resistance | DIN EN 60068-2-27 | 50 g (11 ms) |
|
Vibration resistance | DIN EN 60068-2-6 | 20 g (10…2000 Hz) |
|
MTTF [years] | 323 |
UL Certification | UL Registration Number | J022 | td> |
|
Mechanical data |
---|
Weight [g] | 302 |
Material | stainless steel steel (1.4404 / 316L), PBT (polybutylene terephthalate) medium | Ceramic (99.9% Al2 O3), PTFE (Teflon), st. steel (1.4435 / 316L), surface characteristic: Ra <0.4 / Rz 4 |
Min. pressure cycles | 100 million |
Tightening torque [Nm] | 20, (recommended tightening torque Depending on lubricant , seals and pressure ratings) |
Process connection | G threaded connection 1 external thread Sealing cone |
Displays / Controls |
---|
Display | bar, psi, MPa |
Notes |
---|
Packing quantity | 1 piece |
Electrical connection |
---|
Connection | Connector: 1 x M12, Contacts: gold-plated |