Electronic data |
---|
AC frequency [Hz] | 47…64 |
Operating voltage tolerance [%] | 10 |
Operating voltage tolerance 2 [%] | 10 |
Operating voltage [V] | Auto ranging |
Rated AC voltage [V ] | <230 |
AC input voltage [V] | 100…120 / 200…240 | tr>
Output voltage DC [V] | 24…28 |
Protection class | I, ( IEC 61140) |
Surge protection | Yes, (<39 DC) |
Output voltage [V] | adjustable, output voltage SELV, PELV |
Max. output current at min. output voltage [A] | 5 |
Max. output current at max. output voltage [A] | 4.3 |
Max. output current peak at min. output voltage [A] | 6 |
Max. output current peak at max. output voltage [A] | 5.1 |
Output power (constant) [W] | 120 |
Output power (peak) [W] | 144 |
Note on output power (peak) | ? 45 °C permanently allowed,> 45 °C <1 minute every 10 minutes |
|
Note on power factor (nominal voltage 120 V AC / 60 Hz) | 0.56 |
Note on power factor (nominal voltage 230 V AC / 50 Hz) td> | 0.47 |
Power reserve [%] | 20 |
Number - circuits for connecting safety sensors | 1 |
Max. residual ripple [mV] | 50 |
Peak current at switch-on (nominal voltage 120 V AC / 60 Hz) [A] | 3 |
Peak make current (nominal voltage 230 V AC / 50 Hz) [A] | 3 |
Starting current limitation | yes |
Efficiency (nominal voltage 120 V AC / 60 Hz) [%] | 89.4 |
Efficiency (nominal voltage 230 V AC / 50 Hz) [%] | 90.2 |
Secure external input | ? B-10 A / ? C-6 A |
Derating tolerances [W/K] | 3 (60…70 °C) | tr>
Operating time when power is off (nominal voltage 120 V AC / 60 Hz) [ms] | 80 |
Operating time at power failure (nominal voltage 230 V AC / 50 Hz) [ms] | 78 |
Input current (nominal voltage 120 V AC / 60 Hz) [A] | 2.05 |
Input current (nominal voltage 230 V AC / 50 Hz) [A] | 1 .23 |
Power loss (nominal voltage 120 V AC / 60 Hz) [W] | 14.5 |
Power loss (nominal voltage 230 V AC / 50 Hz) [W] | 13.2 |
Reverse voltage protection [V] | 35 |
Outputs |
---|
Short circuit protection | yes |
Overcurrent protection | yes |
Tolerable overload | permanent output current |
Operating conditions |
---|
Ambient temperature [°C] | -25…70 |
Note on ambient temperature | td> | keep free space for convection (see operating instructions) |
|
Storage temperature [°C] | -40…85 |
Max. permissible relative humidity [%] | 95, (IEC 60068-2-30) |
Degree of protection | IP 20, (EN 60529) |
Pollution degree | 2, (IEC 62103: no conductive pollution allowed) |
Tests / Approvals |
---|
EMC | EN 61000-6-1 | | EN 61000-6-2 | | EN 61000-6-4 | |
|
Vibration resistance | IEC 60068-2-6 | ±1.6 mm 2…17.8 Hz / 2 g 17.8…500 Hz | |
Impact resistance | IEC 60068-2-27 | 30 g 6 ms / 20 g 11 ms |
|
Mechanical data |
---|
Weight [g] | 594.5 |
Mounting | rail, (TH35 (EN 60715)) |
Dimensions [mm] | 124 x 40 x 122.5 |
Material | Steel sheet |
Displays / Controls |
---|
Display | |
Notes |
---|
Notes | Standard connection of outputs only valid for identical devices up to max. 150 V DC total voltage | 100 V AC supply and a constant P> 120 W can lead to thermal shutdown. |
|
Packing quantity | 1 piece |
electrical connection |
---|
Connection | screw terminals: |
diagrams and graphs |
---|
Chart block | |
---|
output characteristics | |
---|
characteristic curve for efficiency level / power loss | |
---|
characteristic line for tolerances from nominal values | |
---|
Characteristic straight line for power down operation time | |
---|