Supply of spare parts for industrial enterprises around the world

IFM AC1258

  IFM AC1258
Manufacturer
IFM
Part number
AC1258
Country
Germany
Sale of any product from the IFM catalog at competitive prices

2technologie will help you choose and buy products and spare parts from IFM (official website: www.ifm.com). We sell only certified goods and give an official guarantee from the manufacturer IFM


Reliably power supply for modules, sensors and actuators. High noise immunity and sufficient power reserves for the compensation of current peaks. Safe decoupling of interferences from the primary supply. Particularly space-saving design. Low heating of the control cabinet due to high efficiency.
Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications AC1258

Electronic data
AC frequency [Hz]47…64
Operating voltage tolerance [%]10
Operating voltage [V]automatic selection range
Rated AC voltage [V]<230
AC input voltage [V] 100…120 / 200…240
Protection classI
Surge protectionyes, (<36)
Max. turn-on delay time [ms]800
Power-on delay time [s]<800
AS-i output voltage [V]30.5
Power output (constant) [W]244
Output power (peak) [W]256
Note on output power (peak)Note on power factor (rated voltage 230 V AC / 50 Hz)
briefly for loading bus bandwidth after power on
Note on power factor (nominal voltage 120 V AC / 60 Hz)0.59
0.51
Power reserve [%]5
Number of circuits for connecting security sensors1
Day off current AS-i [A]8
Max. residual ripple [mV]100
Peak switch-on current (nominal voltage 120 V AC / 60 Hz) [A]3
Peak make current (nominal voltage 230 V AC / 50 Hz) [A]3
Starting current limitationyes
Efficiency (nominal voltage 120 V AC / 60 Hz) [%]89.4
Efficiency (nominal voltage 230 V AC / 50 Hz) [%]90.9
Secure external input? B-10 A / ? C-6 A
Derating tolerances [W/K]6 (60…70 °C)
Operating time at power failure (nominal voltage 120 V AC / 60 Hz) [ms]44
Operating time at power failure (nominal voltage 230 V AC / 50 Hz) [ms]42
Input current (nominal voltage 120 V AC / 60 Hz) [A]3.73
Input current (rated voltage 230 V AC / 50 Hz) [A]2 .23
Power loss (nominal voltage 120 V AC / 60 Hz) [W]28.9
Power loss (nominal voltage 230 V AC / 50 Hz) [W]24.4
Reverse voltage protection [V] 35
Outputs
Short circuit protectionyes
Overcurrent protectionyes
Tolerable overloadpermanent output current
Operating conditions
Ambient temperature [°C]-25…70
Note on ambient temperature td>
keep free space for convection (see operating instructions)
Storage temperature [°C]-40… 85
Max. permissible relative humidity [%]95, (IEC 60068-2-30)
Degree of protectionIP 20
Pollution Degree2, (IEC 62103: no conductive pollution allowed)
Tests / Approvals
EMC
EN 61000-6-1
EN 61000-6-2
EN 61000-6-4
Vibration resistance
IEC 60068-2-6± 1.6 mm 2…17.8 Hz / 2 g 17.8…500 Hz
Impact resistance
IEC 60068-2-2730 g 6 ms / 20 g 11 ms
AS-i classification
AS-i certificate98501
Mechanical data
Weight [g] 883
Mounting methodrail, (TH35 (EN 60715))
Dimensions [mm]124 x 62 x 120
Materialsteel sheet
Displays / Controls
Display
AS-i Bus Power LED, green
Notes
Packing quantity 1 piece
Electrical connection
ConnectionScrew terminals :
charts and graphs
Chart block
output characteristics
characteristic curve for efficiency level / power loss
characteristic straight line for permissible deviations from the nominal values ​​of parameters power