Supply of spare parts for industrial enterprises around the world
Home Brands Euchner 103489 SOM-4E-0A-C1

Euchner SOM-4E-0A-C1 103489

 SOM-4E-0A-C1 Euchner 103489
Manufacturer
Euchner
Name
SOM-4E-0A-C1
Part number
103489
Country
Germany
Sale of any product from the Euchner catalog at competitive prices

2technologie will help you choose and buy products and spare parts from Euchner (official website: www.euchner.de/en-us/). We sell only certified goods and give an official guarantee from the manufacturer Euchner


Order Euchner 103489 Spare Parts Online for Enhanced Efficiency

For industries seeking reliable components, Euchner 103489 Industrial parts are the ideal choice. Built with precision and innovation, these Euchner 103489 spare parts optimize industrial operations across USA.

What Makes 2technologie Stand Out?

  • Comprehensive Options: A full range of Euchner 103489 spares for all applications.

  • Swift Delivery: Quick access to Euchner 103489 spare parts near me or online.

  • Cost-Effective Solutions: Quality Euchner 103489 Industrial products at the best prices.

  • Proven Expertise: A trusted provider of Euchner 103489 Industrial components.

Order Euchner 103489 spare parts today and experience the 2technologie difference!

Worldwide delivery services
Worldwide delivery services
Ways of payment
Ways of payment

Specifications SOM-4E-0A-C1 103489

  • 1 redundant OSSD
  • Control by SMOx/GMOx
  • Control by machine control
  • Up to 4 inputs
  • Diagnostics via AS-Interface
OSSDs (Output Signal Switching Devices)The OSSD is of redundant design according to category 4 EN ISO 13849-1. Safety-related control is via the bus by a suitable monitor, for example by a GMOx or SMOx. Operational switching is also possible directly by the control system with appropriate parameter settings. Inputs and outputsA feedback loop can be connected directly to the SOM. Depending on the parameter settings, further inputs and outputs can also be used. LED function display
PWRGreen, AS-Interface power
ASiRed, bus communication
OUTYellow, state of output signal switching device
ALARMRed, can be set as required by control system
I1...I3State of the corresponding input
1.Y1State of the input
Dimension drawing Wiring diagram Dimension drawingWiring diagram Technical dataApprovals Mechanical values and environment
Housing material Polyamide PA 6.6
Ambient temperature 0 ... 55 °C
Degree of protection IP20
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Reaction time
Safety circuit off max.50 ms
Connection Connection terminals
E1 terminal I1, E2 terminal I2, E3 terminal I3
Number of inputs 3
Output contact set 1: 1.13, 1.14, output contact set 2: 1.23, 1.24
Number of safety contacts 1
Terminal 1.Y1, I+
Number of inputs 1
Electrical connection ratings
ASi voltage
DC 30 V
ASi operating current max.200 mA
Current 0,1 A Supply for sensors
LED indicator
3 LEDs yellow (I1, I2, I3) state of input E1, E2 and E3
1 x LED yellow (1. Y1) state EDM input 1.Y1
LED green (Pwr) AS-i power supply
LED red (Fault) AS-i fault
LED yellow (Out) relay has switched and error message
LED red (Alarm) PLC is signaling alarm
Rated insulation voltage Ui 6000 V
Overvoltage category according to IEC EN 60664-1 3
Connecting cable 9W
Max. contact load
DC -13 3A 24V
AC -15 3A 250V
Terminal 1.Y1, I+
Type of input Feedback loop (EDM)
Current via feedback loop
at 24V DC 10 mA From AS-i (EDM)
Output contact set 1: 1.13, 1.14, output contact set 2: 1.23, 1.24
Type of output
2 NO contacts per safety output Relay contacts, floating, positively driven (redundant)
E1 terminal I1, E2 terminal I2, E3 terminal I3
Type of input standard
Interface, bus
Data interface Address programming socket AS-i (ADDR)
Controls and indicators
Control/indicator
Ausfuhrung
Einlegeschild
Extras
Farbe
Schaltelement
Other
In compliance with EN 61 508, EN 62 061, EN ISO 13 849-1
Reliability values according to EN ISO 13849-1
Performance Level PL e
Category 4
PFHD 3.3 x 10-9
SIL CL 3
Mission time 20 y